ELECTRICAL |
|||||||||||
|
20. |
Receptacles shall be 10' minimum from pool edge. |
680-6a1 |
|||||||||
|
21. |
At least one 125v convenience receptacle between 10' to 20' from pool. |
680-6a2 |
|||||||||
|
22. |
Convenience receptacle and pump cannot be on same circuit. |
210-23a |
|||||||||
|
23. |
Time clock shall be installed so that pump can be set to run in the off peak demand period. |
504.5.3 |
|||||||||
|
24. |
Pump receptacle within 10' from pool edge shall be GFCI, locking, trounding type |
680-6a1 |
|||||||||
|
25. |
Pump receptacle grounding conductor not less than #12AWG, insulated |
6810-25c |
|||||||||
|
26. |
All 125v/15-20A receptacles outdoors to be GFCI. |
210-8a3 |
|||||||||
|
27. |
All light fixtures 5-10' from pool shall be GFCI unless 5' above water. |
680-6b4 |
|||||||||
|
28. |
Switches shall be not less than 5' horizontally from pool, except when located behind a solid barrier. |
680-6c |
|||||||||
|
29. |
Maximum pool equipment flex cord length is 3' (20A or less) except underwater lighting fixtures. |
680-7 |
|||||||||
|
30. |
Wiring method type/Burial depths
|
680-10 |
|||||||||
|
31. |
Bonding required; #8 A WG copper, for following:
|
680-22a |
|||||||||
<back